TP-6804 1/1548 Section 3 RDC2 Controller Operation
3.18.2 Networking Configuration
Submenu (OnCue Password)
The N etworking Configuration menu includes settings
used for communication with the Kohler OnCuer Plus
Generator Management System.
Password
Note: Use the OnCue password s hown on the
controller display for OnCue or OnCue Plus
applications.
For the initial OnCue Plus setup, you will be required to
reset the OnCue password on the RDC2 controller, and
then enter it into the OnCue Plus application. To reset
the password, follow the instructions in Figure 3-21.
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial
number.
A new password is generated each time the reset
password procedure is performed. If the password is
reset after the OnCue Plus system has been set up, the
connection will be lost. Disconnect the battery power to
the controller, wait a minute, then reconnect power.
DHCP Submenu
For most applications, the Dynamic Host Configuration
Protocol (DHCP) is enabled and the IP settings cannot
be changed from the c ontroller keypad. If DHCP is
enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is
required), then the IP parameters can be modified. For
applications that require a static IP address, press and
hold the select button to enable editing, press the down
arrow to disable DHCP, and then step to the next
parameters andenter the information. See Figure 3-21.
If an error occurs while setting a parameter, an error
message is displayed and then the controller exits the
edit mode. Previous settings are preserved.