Kohler 14RESAL-SA2 Portable Generator User Manual


 
TP-6804 1/1532 Section 3 RDC2 Controller Operation
3.2.1 Controller Keypad
The RUN, OFF, and AUTO buttons control the
generator set as described in Figure 3-3.
Use the Select, Up arrow, and Down arrow buttons to
navigate through the menus and change settings, if
necessary. See Section 2.3 for operation instructions.
3.2.2 LED Indicators
LEDs above the RUN, OFF, and AUTO buttons indicate
the mode of operation as shown in Figure 3-4.
Power System LEDs indicate the status of the utility
power and the generator set, and indicate which source
is supplying powerto the building (based on theposition
of the RXT transfer switch). See Figure 3-2 and
Figure 3-4.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected. They will not
operate if a Model RDT or RSB transfer switch is
used.
Button Button Function
RUN Starts the generator set. The engine start time delay is ignored.
OFF Stops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the c rank cycle.
Press OFF to clear faults and reset the controller.
AUTO Places the generator set in Automatic (standby) mode.
Down arrow
Use to navigate through menus and change settings. This manual contains instructions to navigate the
controller menus and adjust settings on the RDC2 controller.
Select
Up arrow
Figure 3-3 RDC2 Controller Pushbutton Operation
LED LED Operation
RUN Lights when the generator set has been started locally by pressing the RUN button.
Remote start and stop commands are ignored.
OFF
Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller
are off. Remote start/stop commands have no effect. The exercise cycle will not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required.
Identify and correct the fault condition before resetting the controller.
AUTO Lights when the generator is in automatic (standby) mode. Generator set will respond to
engine start and stop commands from the controller (for example, exercise start and stop
commands) or an ATS. Time delays operate as described in Section 2.3.
Utility Power Available * Lights when utility power is available.
Building on Utility Power * Lights when the building load is connected to u tility power through the RXT transfer
switch.
Generator Power Available * Lights w hen generator power is available.
Building on Generator Power * Lights when the building load is connected to generator power through the RXT transfer
switch.
* These LEDs operate only if a Model RXT transfer switch is connected.
Figure 3-4 RDC2 Controller LED Operation