TP-6804 12/1140 Section 3 RDC2 Controller Operation
3.14 Genset System Menu
The genset system menu displays the system
information shown in Figure 3-15. Generator sets are
factory set and should not require changes to the system
settings in the field.
A Kohler authorized distributor or dealer can adjust
these settings, if necessary. If the generator set is
reconnected to a different voltage or the system settings
require adjustment for some other reason, see Section
3.5 for instructions to enable editing and change the
system settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the c ontroller
settings. Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
Voltage Regulator (VR) Voltage Adj
The generator set voltage is factory set and typically
does not require adjustment in the field. If voltage
adjustment is required, contact a Kohler authorized
distributor or dealer for service. Refer to the generator
set Installation Manual for instructions to adjust the
voltage.
Setting the Exerciser
Use the Genset System menus to set the generator set
exerciser. Refer to Section 2.4 for instructions to set the
exerciser and for more information about exercising the
generator set.
After a scheduled exercise run, the Next Exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Adjusting the Display Contrast
To adjust the display contrast, use the down arrow
button to step to the Contrast menu. Press the Select
button, and then use the up and down arrow buttons to
adjust the contrast. Press the Select button to save the
contrast setting.
tp6810
Genset ---->
System
System Voltage:
240 V
System Battery:
12 V
System Phase:
Single
<---- Return
Next Exercise
06:30p 15Dec2011
Exercise Freq:
Weekly
Exercise Mode:
Unloaded Variable
System Freq:
60 Hz
Meas System:
English
Contrast:
50
VR Voltage Adj:
240.0V
Figure 3-15 Genset System Menu