Page 16
J-400
7.0 Power Requirements
Jacuzzi
®
spas are designed to provide optimum performance and
exibility of use when connected to their maximum electrical service.
They are congured at the factory. The most common electrical
connections are listed below:
All North American 60 Hz Models only: These models come set for
50A logic. If you prefer, your qualied technician can perform a logic
modication that allows the spas to operate on a different electrical
service (see table footnotes below).
North American J-460/J-465/J-470/J-480 Models (60 Hz)
Voltage: 240 VAC 240 VAC 240 VAC
Max. Current Draw: 23A 36A 45A
Frequency: 60 Hz 60 Hz 60 Hz
Number of Wires: 3 3 3
Circuit Breaker (2-Pole): 30A* 50A** 60A***
*
In 30A conguration, the heater will not operate while either jets
pump is running.
**
In 50A conguration, the heater will not operate while both jet
pumps are running. This is the factory setting.
***
In 60A conguration the heater will operate while both jet pumps
are running.
All Export 50 Hz Models: These models have two terminals
requiring 2 circuit breakers and only have one logic option available.
Export J-460/J-465/J-470/J-480 Models (50 Hz)
Main
Terminal Breaker*
Heater
Terminal Breaker**
Voltage: 230 VAC 230 VAC
Max. Current Draw: 16.6A 12A
Wattage 3.8 kW 2.6 kW
Frequency: 50 Hz 50 Hz
Number of Wires: 3 3
*
The main terminal breaker is solely for the pumps, circulation
pump, ozone, stereo option (if installed) and accessories.
**
The heater breaker is solely for the heater, to allow the heater to
operate while both jet pumps are running.
Note: Two breakers needed see Figure E page 15.