SECTION 2—PARTS AND INSTALLATION
Side Entry Whirlpool Tub 18 Part No 1118387
ƽ WARNING
All electrical conduit, fittings and wire to unit are to be supplied and installed by a
professional electrician in accordance with the National electrical code as a
minimum requirement, including the supply and installation of a Ground Fault
Circuit Interrupter (GFCI).
For Canadian installation, ground fault interrupter and a 30-minute maximum
timer MUST be installed in the electrical circuit. (Parts not supplied by ICCG). The
unit must be operated through the circuit. The 30-minute timer must be located in
a position where a person in the unit cannot reach the timer.
NOTE:Forthisprocedure,refertoFIGURE 2.4onpage19.
NOTE:Use15AMPGFCIbreakeronly.
1. Ensurea15AMPGFCIbreakerisinstalledtoprotecttheunit.
2. Connectthegreenterminaltothegroundingterminaloftheelectricservicesupply
panelusingacontinuousgreeninsulatedcopperwireequivalentinsizetothecircuit
conductorssupplyingthisequipment,butnosmallerthanNo.8AWG(3.3mm).
NOTE:Thegreenterminalmaybeawireconnectormarked“G”,“GR”,“Ground”or
“Grounding”.
3. UsethepressurewireconnectorontheexterioroftheterminalboxtoconnecttheNo.
8AWG(8.4mm)solidcopperbondingconductorbetweentheunitandallother
electricalequipmentandexposedmetalinthevicinity,tocomplywithlocal
requirements.
4. UseapneumaticairswitchwiththepushbuttonlocatedonthetubdeckforOn/Off
switching.
5. Installa115Velectricalhook‐upperlocalelectricalcodesthroughadedicatedGFCI
circuit(Detail“A”).
6. Removeserviceaccesspanelbyremovingscrews,inordertoaccesspumpelectric
connections.
7. Routeelectricallinethroughelectricallineroutingholeinbackpanel.
8. Removethemotorcover(Detail“C”).
9. Connectground,neutralandhotwiresfromwalldirectlytomotorthroughthe
electricallineroutinghole
inthebackpanel(Detail“D”).