Honeywell T775J Weather Radio User Manual


 
T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER
63-2248—4
15
4-20 mA: This is a general purpose current mode output that can drive a 600 ohm maximum load without output current
1234
OPEN
A
C
B
D
1234
OPEN
A
C
B
D
1234
OPEN
A
C
B
D
1234
OPEN
A
C
B
D
A. SWITCH 1 CONTROLS THE RESET DIRECTION.
LEFT RESETS SENSOR A CONTROL POINT (BOILER OR CHILLER WATER TEMPERATURE UP;
RIGHT RESETS IT DOWN.
B. SWITCH 2 CONTROLS THE RESET ACTION.
LEFT RESETS AS SENSOR B (OUTDOOR TEMPERATURE) DROPS BELOW SETPOINT B;
RIGHT RESETS AS IT RISES ABOVE IT.
C. SWITCHES 3 AND 4 ARE NOT USED.
RESETS CONTROL SETPOINT A DOWN
WHEN SENSOR B (OUTSIDE
TEMPERATURE) IS BELOW SETPOINT.
RESETS CONTROL SETPOINT A DOWN
WHEN SENSOR B (OUTSIDE
TEMPERATURE) IS ABOVE SETPOINT.
RESETS CONTROL SETPOINT A UP
WHEN SENSOR B (OUTSIDE
TEMPERATURE) IS BELOW SETPOINT.
RESETS CONTROL SETPOINT A UP
WHEN SENSOR B (OUTSIDE
TEMPERATURE) IS ABOVE SETPOINT.
SETPOINT "B" (OUTSIDE TEMPERATURE)
BELOW ABOVE
UPDOWN
M4719