Air-cooled 11 kW Generators
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Model 04916-0
Rated Max. Continuous Power Capacity (Watts*) 10,000 NG/11,000 LP
Rated Voltage 120/240
Rated Max. Continuous Load Current (Amps)
120 Volts** 83.3 NG/91.7 LP
240 Volts 41.7 NG/45.8 LP
Main Line Circuit Breaker 45 Amp
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60 Hz
Power Factor 1
Recommended Air Filter Part # C8127
Battery Requirement Group 26/26R 12 Volts and
at -17.8° C (0° F) 525 Cold-cranking Amperes Minimum
Weight 495 Pounds
Output Sound Level @ 23 ft (7m) at full load 62.2 db (A)
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for 240
volts.
1.6.2 ENGINE
Model 04916-0
Type of Engine GT-990
Number of Cylinders 2
Rated Horsepower 30 @ 3,600 rpm
Displacement 992cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valves
Ignition System Solid-state w/Magneto
Recommended Spark Plug RC14YC
Spark Plug Gap 0.76 mm (0.030 inch)
Compression Ratio 9.5:1
Starter 12Vdc
Oil Capacity Including Filter Approx. 1.7 Qts
Recommended Oil Filter Part # 70185
Recommended Air Filter Part # 0C8127
Operating RPM 2,700