Generac Power Systems 004090-2, 004091-2, 004092-2, 004093-2, 004094-2, 004095-2, 004096-2, 004097-2 004474-0, 004124-1, 004125-1, 004126-1, 004127-1, 004128-1, 004130-1, 004131-1, 004475-0 Portable Generator User Manual


 
INSPECTION:
After unpacking, carefully inspect the generator for any
damage that may have occurred during shipment. If
loss or damage is noted at the time of delivery, have the
person(s) making delivery note all damage on the freight
bill or affix his signature under the consignor’s memo of
loss or damage.
LIFTING THE GENERATOR
WARNING: When lifting or hoisting equipment is used,
be careful not to touch overhead power lines. The gener-
ators weight of more than 900 pounds requires proper
tools, equipment, and qualified personnel to be used in
all phases of handling and unpacking.
SPECIFICATIONS
ENGINE SPECIFICATIONS
Make................................................................................Mitsubishi
Displacement ................................................92 inches
3
(1.5 liters)
Cylinder Arrangement........................................................4, in-line
Valve Arrangement..................................................Overhead Cam
Firing Order..........................................................................1-3-4-2
Number of Main Bearings ............................................................5
Compression Ratio ................................................................9 to 1
No. of Teeth on Flywheel ..........................................................104
Ignition Timing
at 1800 rpm ....................................................35 degrees BTDC
at 3600 rpm ....................................................43 degrees BTDC
Spark Plug Gap ....................................................0.020-0.025 inch
Recommended Spark Plugs
Champion ......................................................................RN11YC4
Oil Pressure......................................................................30-50 psi
Crankcase Oil Capacity..........................4.0 U.S. quarts (3.8 liters)
Recommended Engine Oil..........................................SAE 15W-40
Type of Cooling System ....................Pressurized, closed recovery
Cooling Fan ................................................................Pusher Type
Cooling System Capacity ........................2 U.S. gallons (7.6 liters)
Recommended Coolant..............................Use a 50-50 mixture of
ethylene glycol base.
FUEL CONSUMPTION
Models 004096, 004097, 004130, 004131, 004474, 004475
Using Natural Gas ....................................441 cu. ft. per hour
Using LP Gas ........................175 cubic ft.(4.8 gal.) per hour
Models 004094, 004095, 004126, 004127
Using Natural Gas ....................................359 cu. ft. per hour
Using LP Gas ........................143 cubic ft. (4.0 gal.) per hour
Model 004092, 004093, 004128
Using Natural Gas ....................................277 cu. ft. per hour
Using LP Gas ........................110 cubic ft.(3.1 gal.) per hour
Models 004090, 004091, 004124, 004125
Using Natural Gas ....................................195 cu. ft. per hour
Using LP Gas ..........................77 cubic ft. (2.2 gal.) per hour
NOTE:
Fuel consumption is given at rated maximum con-
tinuous power output when using natural gas rated
at 1000 Btu per cubic foot; or LP gas rated 2520
Btu per cubic foot. Actual fuel consumption
obtained may vary depending on such variables as
applied load, ambient temperature, engine condi-
tions and other environmental factors.
TORQUE SPECIFICATIONS
Cylinder Head......................................15 (+ 90° + 90°) ft.lb.
Intake Manifold..........................................................13 ft.lb.
Exhaust Manifold ......................................................13 ft.lb.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the
factory. Use a high-quality detergent oil classified “For
Service CC, SD, SE, SF.” Detergent oils keep the engine
cleaner and reduce carbon deposits. Use oil having the
following SAE viscosity rating, based on the ambient
temperature range anticipated before the next oil
change:
CAUTION: Any attempt to crank or start the
engine before it has been properly serviced with
the recommended oil may result in an engine
failure.
Section 1 — General Information
Guardian Liquid-cooled 10 kW, 15 kW, 20 kW and 25 kW Generators
Generac
®
Power Systems, Inc. 7
Temperature Oil Grade (Recommended)
Above 80° F (27° C) SAE 30W or 15W-40
32° to 80° F (-1° to 27° C) SAE 20W-20 or 15W-40
Below 32° F (0° C) SAE 10W or 15W-40