Generac 101 9-3 Portable Generator User Manual


 
15
7500EXL Extended Life Generator
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power
at 30 Amps.The outlet is protected by a 30 Amp
push–to–reset circuit breaker.
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 14).You can use the same 4–wire cord if
you plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
30 Amps for 120 Volts; 7,200 watts of power (7.2 kW) at
30 Amps for 240 Volts.The outlet is protected by a 30 Amp
push–to–reset circuit breaker.
120/240 Volt AC, 50 Amp Receptacle
Use a NEMA 14–50 plug with this receptacle (Figure 15).
Connect a 4-wire cord set rated for 250 Volt AC loads at
50 Amps to the plug.
Use this receptacle to operate 120/240 Volt AC, 60 Hz,
single phase loads requiring up to 7,500 watts (7.5 kW) of
power.The outlet is protected by a 35 Amp push–to–reset
circuit breaker.
Figure 15 — 120/240 Volt AC, 50 Amp Receptacle
NEMA 14-50
120 Volts
AC
120 Volts
AC
W (Neutral)
Frame Ground
X (Hot)
Y (Hot)
240 Volts AC
Figure 14 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
Figure 13 — 120 Volt AC, 30 Amp, Locking Receptacle
3-Wire Cord Set
Neutral
120V
Hot
Ground (Green)
NEMA L5-30