Energy Tech Laboratories RSIB 300-500 Blower User Manual


 
7
3002503 11.06
Sidewall
Venting
Vertical
Venting
Thegurebelow shows typical installation arrangements:
3.3 Mounting of Power Venter
The power venter can be installed in a variety of positions. It can be
suspendedfromaceilingorplacedonashelf/oor.Placementona 
shelf requires special hardware and vibration dampers.
Suspension from a ceiling does not require any special hardware
other than threaded rods, nuts, and hangers.
Follow Fig. 4 and 5. when suspending the power venter from a
ceiling. Fig. 4 shows which mounting legs to use when installing
the power venter in its normal position with inlet in the back and
outlet on the top (installation between horizontal and vertical
chimney). Fig. 5 shows which mounting legs to use when installing
the power venter with inlet on the bottom and outlet on the side
(installation for sidewall venting).
1. Once the position has been determined, hang four threaded
rods from hangers above, and slide the rods through the mounting
holes in the mounting legs.
2. Level the power venter.
3. Secure the legs with washers and nuts.
Warning! Never install the power venter so the motor
points down. This will shorten the life. The min.
clearance to combustibles is 24 inches.
Threaded rod
Nuts
Mounting legs
UP
Threaded
rods
Mounting
legs
UP
Nuts
Fig. 3
Fig. 4
Fig. 5