Cal Spas 5100 Hot Tub User Manual


 
2008 Portable Spa Owner’s Manual Page 5
LTR20081000, Rev. B
Preparing for Your New Portable Spa
Spa Model GFCI Required Wires Required
All 240V spas (except 6300 control boxes requiring
high amperage - see below)
One 50 amp GFCI Four #8 AWG copper wires
Spas with the 6300 control box (when high amperage
is selected on circuit board)
SEE CONFIGURATION INSTRUCTIONS BELOW.
One 60 amp GFCI Four #8 AWG copper wires
Ultimate Fitness spas with one 5.5 kW heater One 50 amp GFCI Four #8 AWG copper wires
Ultimate Fitness spas with two 5.5 kW heaters Service 1: One 50
amp GFCI
Service 2: One 30
amp GFCI
Service 1: Four #8 AWG copper
wires
Service 2: Three #8 AWG copper
wires
Testing the GFCI Breaker
Test the GFCI breaker prior to rst use and periodically
when the spa is powered. To test the GFCI breaker
follow these instructions (spa should be operating):
Press the TEST button on the GFCI. The GFCI will trip
and the spa will shut off.
Reset the GFCI breaker by switching the breaker to the
full OFF position, wait a moment, then turn the breaker
back on. The spa should have power again.
Conguring the 6300 Control System
The 6300 control system requires higher power than
other 240V systems. Dip switch #10 is factory set in the
ON position. This causes the heater to shut off when
any pump is running in high speed. To allow the heater
to continue operating, dip switch #10 must be set to the
OFF position.
To ensure your spa functions properly, ensure the
following steps are performed before starting your spa:
When installing the electrical system, use a 60 amp
GFCI. Follow the GFCI wiring diagram on the next
page.
Have your dealer or installer set dip switch #10 to the
OFF position on the circuit board as shown below.