Briggs & Stratton Year 2010 Portable Generator User Manual


 
21
Troubleshooting
Problem Cause Correction
Engine is running, but no AC output
isavailable.
1. Circuit breaker open or defective.
2. Fault in generator control panel.
3. Poor wiring connections or
defective transfer switch.
1. Reset or replace circuit breaker.
2. Contact local service facility.
3. Check and repair.
Engine runs good at no-load but “bogs
down” when loads are connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
4. Fuel pressure or mixture is
incorrect.
5. Kinked fuel line.
1. Disconnect shorted electrical load.
2. Turn off one or more loads.
3. Contact local service facility.
4. See Gaseous Fuel System in the
Installation Manual.
5. Remove kink. Replace if necessary.
Engine will not start; or starts and
runsrough.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
4. Fuel pressure is incorrect
1. Install (new) 15 Amp fuse. See
System Control Panel.
2. Open fuel valve(s); check
propanetank.
3. Replace battery.
4. See Gaseous Fuel System in the
Installation Manual.
Engine shuts down during operation.
1. Fuel supply turned off or depleted.
2. Fault indicator blinking.
1. Check fuel valves, fill propane tank.
2. Count blinks and refer to Fault
Detection System.
Loss of power on circuits.
1. Generator circuit breaker is open.
2. Transfer switch problems.
1. Reset circuit breaker.
2. See the transfer switch manual.