Baldor GLC50 Portable Generator User Manual


 
Series GLC A-9MN2408
GLC Wire Size
Revision B 5–12–04
Circuit
Breaker
Size
Quantity per
Phase
Minimum
Wire Gauge
EDI Plant Ampacity @125C
15 1 #16 1 - #14 EPDM PER PHASE 40
20 1 #16 1 - #14 EPDM PER PHASE 40
30 1 #14 1 - #8 EPDM PER PHASE 90
40 1 #12 1 - #8 EPDM PER PHASE 90
50 1 #10 1 - #8 EPDM PER PHASE 90
60 1 #8 1 - #8 EPDM PER PHASE 90
70 1 #8 1 - #8 EPDM PER PHASE 90
80 1 #6 1 - #8 EPDM PER PHASE 90
90 1 #6 1 - #6 EPDM PER PHASE 125
100 1 #6 1 - #6 EPDM PER PHASE 125
110 1 #6 1 - #6 EPDM PER PHASE 125
125 1 #4 1 - #4 EPDM PER PHASE 170
150 1 #2 1 - #4 EPDM PER PHASE 170
175 1 #2 1 - #1 EPDM PER PHASE 265
200 1 #1 1 - #1 EPDM PER PHASE 265
225 1 1/0 1 - #1 EPDM PER PHASE 265
250 1 2/0 1 - #1/0 EPDM PER PHASE 305
300 1 4/0 1 - #2/0 EPDM PER PHASE 355
350 1 4/0 1 - #3/0 EPDM PER PHASE 410
400 2 #1 1 - #4/0 EPDM PER PHASE 475
450 2 1/0 2 - #1/0 EPDM PER PHASE 610
500 2 1/0 2 - #1/0 EPDM PER PHASE 610
600 2 3/0 2 - #2/0 EPDM PER PHASE 710
700 2 4/0 2 - #3/0 EPDM PER PHASE 820
800 3 2/0 2 - #4/0 EPDM PER PHASE 950
900 3 3/0 3 - #2/0 EPDM PER PHASE 1065
1000 3 3/0 3 - #3/0 EPDM PER PHASE 1230
1200 3 250 3 - #4/0 EPDM PER PHASE 1425
1400 4 4/0 4 - #4/0 EPDM PER PHASE 1900
1600 4 250 4 - #4/0 EPDM PER PHASE 1900
2000 5 250 5 - #4/0 EPDM PER PHASE 2375
2500 6 250 6 - #4/0 EPDM PER PHASE 2850
3000 7 250 6 - #250 EPDM PER PHASE 3180
4000 8 300 8 - #250 EPDM PER PHASE 4240
Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.