A-8 Series GLC MN2408
GLC DATA
Continued
GLC
Alternator Engine Output
GLC
Model
Model
Leads/
Winding
Fuel
Type
Size
KW
Rated
Phase
Voltage
Config
VAC
(L - L)
VAC
(L - N)
FLA
115%
FLA
Circuit
Breaker
C.T.
Ratio
Wire Size
(QTY) AWG
GLC30 BCI184G 4/06 Nat Gas GM/4.3L 30 1 Series 240 120 125 144 150 150:5 (1) #4
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 // WYE 208 120 104 120 125 125:5 (1) #4
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 // WYE 220 127 98 113 125 125:5 (1) #4
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 Series/
Delta
240 120 90 104 110 125:5 (1) #6
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 // WYE 240 139 90 104 110 125:5 (1) #6
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 Series
Wye
380 220 57 66 70 75:5 (1) #8
GLC30 UCI224C 12/311 Nat Gas 3 416 0
GLC30 UCI224C 12/311 Nat Gas GM/4.3L 30 3 Series
Wye
480 277 45 52 60 60:5 (1) #8
GLC30 BCI184G 4/06 LPG GM/4.3L 30 1 Series 240 120 125 144 150 150:5 (1) #4
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 // WYE 208 120 104 120 125 125:5 (1) #4
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 // WYE 220 127 98 113 125 125:5 (1) #4
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 Series/
Delta
240 120 90 104 110 125:5 (1) #6
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 // WYE 240 139 90 104 110 125:5 (1) #6
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 Series
Wye
380 220 57 66 70 75:5 (1) #8
GLC30 UCI224C 12/311 LPG 3 416 0
GLC30 UCI224C 12/311 LPG GM/4.3L 30 3 Series
Wye
480 277 45 52 60 60:5 (1) #8