4-2. GAS CHARGE
Perform gas charge to unit.
1 Connectgascylindertotheserviceportofstopvalve.
2 Performairpurgeofthepipe(orhose)comingfromrefrigerantgas
cylinder.
3 Replenishspecied
amountoftherefrigerant,whileoperatingtheair
conditioner for cooling.
Note:
Incase
ofaddingrefrigerant,complywiththequantityspeciedforthe
refrigeratingcycle.
CAUTION:
Whencharging
therefrigerantsystemwithadditionalrefrigerant,besure
touseliquidrefrigerant.Addinggasrefrigerantmaychangethecomposi-
tionof
therefrigerantinthesystemandaffectnormaloperationoftheair
conditioner.Also,chargethesystemslowly,otherwisethecompressor
will be locked.
Tomaintainthehighpressureofthegascylinder,warmthegascylinder
withwarmwater[under40°C(140°F)]duringcoldseason.Butneveruse
nakedreorsteam.
Union
Stop valve
Liquid pipe
Union
Union
Union
Indoor
unit
Stop valve
with
service port
Gas pipe
Refrigerant gas
cylinder
operating valve
(for
R410A)
Gauge manifold
valve(forR410A)
Chargehose(forR410A)
Refrigerantgascylinder
for R410A with siphon
Electronic scale for
refrigerant charging
Refrigerant(liquid)
Outdoor unit
(MXZ-4A36NA)
Service port cap
(Torque 13.7 to
17.7 N•m, 140 to
180 kgf•cm, 10
to
13 ft•lb)
4-1. PURGING PROCEDURES AND LEAK TEST
Stop valve
for GAS
Stop valve cap
(Torque 19.6 to 29.4 N•m,
200 to 300 kgf•cm, 15 to
22ft•lb)
Gauge manifold
valve(forR410A)
Compound pressure
gauge(forR410A)
–0.101MPa
[–760 mm
Hg
(–30in.Hg)]
Handle
Low
Handle
High
Vacuum
pump
(forR410A)
Charge hose
(forR410A)
*Close
*Open
Hexagonal wrench
*4
to 5 turns
Stop valve
for LIQUID
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Pressure gauge
(forR410A)
Precautions when using
the control valve
When attaching the control valve to
theserviceport,valvecoremayde-
form or loosen if excess pressure is
applied.Thismaycausegasleak.
Service port
Charge hose
(forR410A)
Body
Close
Open
Control
valve
A
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten part A. Do not tighten
partAorturnthebodywhenvalve
core is in open position.
1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunit
gas pipe. (The stop valve will not work in its initial state fresh out of the
factory,totallyclosedwithcapon.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportof
stop valve on the gas pipe side of the outdoor unit.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)
4)Checkthevacuumwithgaugemanifoldvalve,thenclosegaugemani
-
fold valve,
and stop the vacuum pump.
5)Leaveasitisforoneortwominutes.Makesurepointergaugemani-
foldvalveremains
inthesameposition.Conrmthatpressuregauge
shows–0.101Mpa[Gauge][–760mmHg(–30in.Hg)].
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)Afterrefrigerantpipesareconnectedandevacuated,fullyopenall
stop valves on both sides of gas pipe and liquid pipe. Operating with
-
outfully
openinglowerstheperformanceandthiscausestrouble.
8)Referto1-4.,andchargetheprescribedamountofrefrigerantif
needed.Besuretochargeslowlywithliquidrefrigerant.Otherwise,
compositionoftherefrigerantinthesystemmaybechangedandaf
-
fect performance
of the air conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10)Leaktest