Installation Drawings
13
Figure 4 Outline drawing, 250kVA Liebert NXL UPS
71.8"
(1823mm)
34.8"
(884mm)
33.5"
(850mm)
76.8"
(1950mm)
17.6"
(448mm)
56.8"
(1443mm)
8.5
(216)
8.5
(216)
26.1
(664mm)
27"
(685mm)
9.8"
(250)
9.8"
(250)
9.8"
(250)
9.8"
(250)
3.1" (80) (typ)
4.5
(115)
4.7 (120) (typ.)
8.5
(216)
8.3
(210)
CG
B
A
12.1"
(308mm)
12.8"
(324mm)
22.6"
(575)
21.9"
(555)
6.9"
(175)
Detail B
Detail A
Top View (Doors Open)
NOTES:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required
for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run
in separate conduits.
7. Aluminum and copper-clad aluminum cables
are not recommended.
8. Widths are with side panels. the width is 70" (1778mm) without side panels.
9. The depth dimension includes the front door and rear panel.