A SERVICE OF

logo

8
Table 2 – ARI COOLING RATING TABLES
COOLING MODE
548J*
NOMINAL
CAPACITY
(TONS)
NET COOLING
CAPACITY
(BTUH)
TOTAL
POWER
(kW)
SEER EER IPLV
04A 3 37,000 3.3 13.40** 11.00 N/A
05A 4 47,000 4.1 13.10** 11.20 N/A
06A 5 61,500 5.5 13.20** 11.15 N/A
07A 6 70,000 6.3 N/A 11.10 N/A
08D 7.5 88,000 7.8 N/A 11.20 12.40
09D 8.5 99,000 8.8 N/A 11.20 12.40
NOTE:
All AHRI ratings are based on 230, 460 and 575 vo lt.
** Electric Drive (direct drive) X13 5 speed/torque motor. SEER rating is 13.0 for belt drive.
NA Not applicable
HEATING MODE
548J* HSPF
HEATING, LOW HEATING, HIGH
CAPACITY
(BTUH)
COP
CAPACITY
(BTUH)
COP
04A 7.70 18,200 N/A 35,600 N/A
05A 7.70 23,600 N/A 45,500 N/A
06A 7.70 31,200 N/A 58,000 N/A
07A N/A 34,800 2.25 67,000 3.30
08D N/A 48,000 2.25 86,000 3.30
09D N/A 54,500 2.25 96,000 3.30
LEGEND
ARI --- Air---Conditioning, Heating and Refrigeration
Institute
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
COP --- Coefficient of Performance
EER --- Energy Efficiency Ratio
HSPF --- Heating Seasonal Performance Factor
IPLV --- Integrated Part Load Value
SEER --- Seasonal Energy Efficiency Ratio
Thisproduct hasbeen designedand manufactured to
meet EnergyStar® criteriafor energyefficiency.
However,properrefrigerant chargeand proper airflow
arecriticaltoachieveratedcapacityandefficiency.
Installationofthisproductshouldfollowall
manufacturer’srefrigerantchargingandairflow
instructions.Failuretoc onfirmproperchargeand
airflowmayreduce energyefficiency andshorten
equipment life.
NOTES:
1. Rated and certified under ARI Standard 210/240---06 or
340/360---07, as a ppropriate.
2. Ratings are based on:
Cooling Standard: 80_F(27_C) db, 67_F(19_C) wb indoor air
temp and 95_F db outdoor air temp.
IPLV Standard:80_F(27_C) db, 67_F(19_C) wb indoor air
temp and 80_F(27_C) db outdoor air temp.
3. All 548J units comply with ASHRAE 90.1 2001, 2004 Energy
Standard for minimum SEER and EER requirements.
4. Where appropriate, 548J units comply with US En ergy Policy
Act (2005). Refer to state and local codes or visit the following
website: http://bcap---energy. org to determine if compliance
with this standard pertains to your state, territory, or
municipality.
548J