York LA300 Blower User Manual


 
036-21335-002-A-1102
Unitary Products Group 7
TABLE 3: CORNER WEIGHTS
UNIT-
MODEL
Unit Weight
Configuration A B C DShipping Operation
LA300 1180 1125
HORIZONTAL 276 317 285 247
VERTICAL 262 301 301 262
LB360 1180 1146
HORIZONTAL 281 323 290 252
VERTICAL 266 307 307 266
LB480 1510 1426
HORIZONTAL 348 414 361 303
VERTICAL 292 348 427 359
LB600 1572 1640
HORIZONTAL 451 386 370 433
VERTICAL 484 414 342 400
TABLE 4: ACCESSORY OPERATING WEIGHT DISTRIBUTION (LBS)
1
ACCESSORY
LA300 LB360 LB480 LB600
BASE
2
25 25 30 45
HOT WATER COIL
35 35 45 35
STEAM COIL 1 ROW
30 30 35 50
1.
These weights should be added to each point load in table 3.
2.
This accessory can only be applied on units installed in the vertical position.
TABLE 5: UNIT BLOWER MOTOR DATA
UNIT MODEL HP
MOTOR KIT
MODEL NUMBER
FRAMESIZE
VOLTAGE
(3PH-60HZ)
LA300
5
2LR04605032
184
230/460
2LR04605023 208
2LR04605158 575
7.5
2LP04607133
213
230/460
2LP04607158 575
LB360
5
2LR04605032
184
230/460
2LR04605023 208
2LR04605158 575
7.5
2LP04607133
213
208/230/460
2LP04607158 575
10
2LP04610133
215
208/230/460
2LP04610158 575
LB480
7.5
2LP04607133
213
208/230/460
2LP04607158 575
10
2LP04610133
215
208/230/460
2LP04610158 575
LB600
10
2LP04610133
215
208/230/460
2LP04610158 575
15
2LP04615133
254
208/230/460
2LP04615158 575