4.40 WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Global
Event Input 1
Select the effect of closing the event input 1 switch.
[``no] disables event input 1.
[`LOC] locks out the front panel keys.
[`ALr] resets an alarm.
[A-M] switches the controller to manual mode at the power level set at
[FAIL] (Global Menu) and disables the Auto/Man åkey.
[`OFF] turns all control outputs off (de-energize relays).
[`Pid] switches from PID A to PID B.
[Actn] selects the opposite control action for output 1 and 2.
[`rSP] switches to a remote set point.
[IdSP] switches to an idle or second set point.
[`Ei1] This prompt always appears.
Default
[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [`rsp] [IdSP]
[`Ei1] [`Ei1] [`Ei1] [`Ei1] [`Ei1] [`Ei1] [`Ei1] [`Ei1] [`Ei1]
Event Input 2
Select the effect of closing the event input 2 switch. The selections are
the same as for event input 1.
[`Ei2] This prompt appears only on controllers equipped with hardware
for a second event input (98_ _-_5_ _-_ _ _ _) and with [`In2] set to
[`Ei2].
Default
[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [IdSP]
[`Ei2] [`Ei2] [`Ei2] [`Ei2] [`Ei2] [`Ei2] [`Ei2] [`Ei2]
[`Ei1]
[`Ei2]