Subaru R-134A Backyard Playset User Manual


 
General Preparations
Always conduct a visual inspection of the air conditioning system to identify
any damage, excessive wear, refrigerant leaks (oil residue), improper belt adjust-
ment, improper pulley alignment, and plugged condenser cooling fins.
Note: Never use water to clean the condenser or radiator fins. Using compressed
air is the approved method.
Observe the refrigerant flow through the receiver/dryer sight glass (if
equipped), use the correct gauges to check all systems, verify all system compo-
nents and controls are operable, check for loose fittings, replace defective, worn, or
damaged drive belts, and repair system leaks.
Note: The use of the sight glass alone to determine system charge level can be
misleading. Normally operating and correctly charged variable displacement
compressors and R-134a systems will have bubbles showing in the sight
glass under certain conditions.
Discharging
Caution: Refrigerant R-12 has been identified as a compound which causes
damage to the ozone layer. It is unlawful to discharge R-12 into the atmosphere.
Subaru of America encourages you to handle R-12 in a responsible and safe
manner, and according to Federal EPA guidelines and any local and state regulations.
Always follow approved recovery/recycling procedures and utilize approved
recovery/recycling equipment.
Discharging and recovery of the system refrigerant is required before replacement
of major components of the system. It is also required when the system has a leak,
or for the replacement of refrigerant oil. Discharging and recovery of the system
refrigerant is the first step in preparing for major servicing, repair,
or replacement of components; the second step is evacuation.
Evacuating
Evacuating the system removes air and moisture from the system.
Discharge and recover the system refrigerant first; then follow the
steps listed below to evacuate the system:
Fully close both valves of the manifold gauge set.
Connect a vacuum pump to the center charging hose of
the manifold gauge set.
Start the vacuum pump.
Open the low- and high pressure valves slowly.
When the pressure reading has reached approximately 29.00
in Hg, fully close both valves.
Stop the vacuum pump.
Wait 10 minutes, the pressure reading should not change.
If it changes, there is a leak in the system.
Note: Certain types of system leaks such as loose fittings may not
be discovered using this method. Always recheck the system
with a leak detector after the system is charged.
Elevation Vacuum of System
m (ft) mm Hg, in Hg
0 (0) 710 27.95
300 (1,000) 685 26.97
600 (2,000) 660 25.98
900 (3,000) 635 25.00
Note: Values show readings of the low-pressure gauge.
Evacuating The System
Elevation/Pressure Relationship
9