Subaru Robin Power Products RGV4100 Portable Generator User Manual


 
-
72
-
(4) Check the wiring through ZCT on the IDLE
CONTROL UNIT.
* Single Voltage Type
Make sure that an output wire from main coil is
passing through the ZCT on the IDLE CONTROL
UNIT.
* Dual Voltage Type
Check that two output wires (black wire and red
wire) from main coils are passing through the
ZCT on the IDLE CONTROL UNIT in the same
direction.
(5)
Checking the IDLE CONTROL UNIT (RGV4101)
Check the resistance between five leads of
IDLE CONTROL UNIT with circuit tester.
NOTE : The resistance readings vary depending on the types of circuit testers. The above table shows
an example of the resistance readings measured by an ordinary analogue circuit tester with 1.5
volt battery power source. It is advisable for you to check the resistance readings using your
standard circuit tester and revise the checking table.
Fig. 2-18B
Fig. 2-17
Fig. 2-18A
Table. 2-6
yrettabhtiw(retsettiucriC
)V5.1ecruosrewop
retsettiucricehtfoeldeen)sunim(kcalbylppA
12345
eldeen)sulp(derylppA
retsettiucricehtfo
1----------- k052 k052 k57
2 -----------
3k052 -----------k052 k57
4k052 k052 -----------k57
5k5.8 k8.7 k8.7 -----------