Table 3-1.7
3
Level 1
C.V.
S
L.A.
R.A.
R.V.
Level 2
C.V.
S
L.A.
R.A.
R.V.
NFPA-110
NFPA99
C.V.
S
L.A.
R.A.
R.V.
②
CAN/CSA
C282-M89
C.V. S L.A. R.A. R.V.
A901
C.V.
S L.A. R.A. R.V.
A902
C.V. S L.A.
R.A.
R.V.
④ ④
A903
C.V.
S
L.A.
R.A. R.V.
④ ④
a. Overcrank X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
b. Low Water Temperature X — X X X X — X O O X — X X X X — X X X X — X X X X — X O O X — X O O
c. High Engine Temp. Prealarm X — X X X O — O — O X — X X X O — O O O X — X X X — — — — — — X O O
d. High Engine Temperature X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
e. Low Lube Oil Pressure Prealarm X — X X X X X O — O X — X X X O — O O O X — X X X — — — — — — X O O
f. Low Lube Oil Pressure X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
g. Overpeed X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
h. Low Fuel Main Tank X — X X X O — O O O X — X X X X — X X X X — X X X — — — — — — X O O
i. Control Switch not set in Auto X — X X X O — O — O — — — — — X — X X X X — X X X — — O — O — — — —
j. High Battery Voltage X — X — X O — O — O — — — — — — — — — — X — X — X — — O — O — — — —
k. Low VoltageBattery X — X — X O — O — O — — — — — X — X X X X — X — X — — O — O — — — —
l. Lamp Test X — — — X X — — — — — — — — — X — — — — X — — — — X — — — — X — — — —
m. Audible Alarm Silencing switch — — X X — — — — O — — — — — — — — X X — — — — X — — — — O — — — X O —
n. Low Starting Air Pressure X — X — X O — O — O — — — — — X — X X X — — — — — — — — — — — — — — —
o. Low Starting Hydraulic Pressure X — X — X O — O — O — — — — — X — X X X — — — — — — — — — — — — — — —
q. Remote Emergency Stop — X — — — — X — — — — — — — — — O — — — — X — — — — X — — — — X — — —
r. Low Coolant Level — — — — — — — — — — — — — — — X — X X X — — — — — — — — — — — — — — —
s. Battery Charger AC Failure X — X — X O — O — O — — — — — — — — — — X — X — X — — O — O — — — —
③③ ③③ ③
③
③
⑤
⑤
⑤
⑤
⑤
⑤
①
①
KEY
C.V.: Control panel-mounted Visual indication.
S: Shutdown of EPS
L.A.: Local Audible contacts.
R.A.: Remote Audible contacts.
R.V.: Remote Visual contacts.
X: Required
O: Optional
①: Items “N” or “O” apply only when applicable as
a starting method.
②: NFPA99 requires an audible alarm for all alarm and
shutdown functions. May be connected to L.A. contacts.
③: Air Damper Closed and is available on -2 models only.
④: R.A. and R.V. relays not supplied in model A902 or
A903, optional.
⑤: Circuits and indicators supplied without labels.
p. Air shutdown dampner when used X X X X X X X X O O — — — — — X X X — X X X X X O O X O O