Multiquip DCA-400SPK Portable Generator User Manual


 
PAGE 50 DCA-400SPK PARTS AND OPERATION MANUAL REV. #0 (06/19/01)
17. Observe the generator's ammeter (Figure 49) and verify
that it reads the anticipated amount of current with
respect to the load. Remember the ammeter will only
display a current reading if the load is in use.
18. The generator will run until manually stopped or an
abnormal condition occurs.
Figure 48. Main and GFCI Circuit Breakers
Figure 49. Ammeter (Load)
A
0
40
60
75
20
16. Turn the MAIN, GFCI and LOAD circuit breakers to their
"ON" position (Figure 48).
DCA-400SPK GENERATOR START-UP PROCEDURE (MANUAL)
Figure 47. Engine Tachometer
13. The engine oil pressure gauge (Figure 45) will indicate
the oil pressure (kg/ cm
2
)
of the engine. Under normal
operating conditions the oil pressure should be
approximately 25 psi.
14. The coolant temperature gauge (Figure 46) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature should be between
165 and 215 degrees Fahrenheit (Green Zone).
WATER
TEMP
Figure 46. Coolant Temperature Gauge
Figure 45. Oil Pressure Gauge
15. The tachometer (Figure 47) will indicate the speed of
the engine when the generator is operating. Under normal
operating conditions this speed should be approximately
1800 RPMs.