GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage change-over board
(Figure 12). To obtain some of the voltages as listed in
Table 7 (see below) will require a fi ne adjustment using
the voltage regulator (VR) control knob located on the
control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 12) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Voltage Change-Over BoardFigure 12.
CAUTION
NEVER attempt to place jumper plates on the voltage
change-over board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Voltages AvailableTable 7.
Three Phase
(Switchable)
208V 220V 240V 416V 440V 480V
Single Phase
(Switchable)
120V 127V 139V 240V 254V 277V
Maximum Amps
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Generator Maximum AmpsTable 8.
Model DCA300SSC
Rated Voltage Maximum Amps
Single Phase 120 Volt 666.7 amps (4 wire)
Single Phase 240 Volt 333.3 amps (4 wire)
Three Phase 240 Volt 722 amps