TP-6804 1/15 53Section 3 RDC2 Controller Operation
3.20 Load Control Menus
The Load Control menu displays the status of the Load
Control Module (LCM) or load shed kit inputs and
outputs, and allows a test of the load control output
relays. This menu appearsonly ifan LCM, load shedkit,
or Model RXT transfer switch with the combined
interface/load management board is connected.
Generator current is displayed as a percent of the
maximum generator capacity. The load control module
adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their
priority. For detailed information about the LCM
operation, refer to TT-1574, provided with the LCM kit.
For the load shed kit, see TT-1609.
Input 1:
In/Active
Output 1:
Add/Shed
Input 2:
In/Active
Output 2:
Add/Shed
Output 3:
Add/Shed
Output 4:
Add/Shed
Output 5:
Add/Shed
Output 6:
Add/Shed
Test Outputs
Push Select
(blinking)
<---- Return
tp6810
Load ---->
Control
Load ---->
Control 1
<---- Return
Generator
Current: 123 %