Generac Portable Products SE10000 Generator
10
Use this receptacle to operate 120 Volt AC, 60 Hz,
single phase loads requiring up to 3600 watts
(3.6 kW) of power at 30 Amps. The outlet is protected
by a 30 Amp push-to-reset circuit breaker.
120/240 Volt AC, 30 Amp Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect a suitable 4-wire grounded cord set to the
plug and to the desired load (Figure 11). The cord set
should be rated for 250 Volts at 30 Amps (or greater).
Use this receptacle to operate 120 Volt AC, 60 Hz,
single phase loads requiring up to 3600 watts
(3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz,
single phase loads requiring up to 7200 watts
(7.2 kW) of power at 30 Amps. The outlet is protected
by a 30 Amp pushtoreset circuit breaker.
240 Volt AC, 50 Amp Receptacle
Use a NEMA 1450 plug with this receptacle.
Connect a 4-wire cord set rated for 250 Volts at
50 Amps to the plug (Figure 12).
Use this receptacle to operate 240 Volt AC, 60 Hz,
single phase loads requiring up to 10,000 watts
(10.0 kW) of power.
CAUTION! Although this outlet states it has a
240 Volt AC, 50 Amp rating (up to 12,500
watts), the generator is only rated for 10,000
watts. Powering loads that exceed the wattage/
amperage capacity of the generator can
damage it and cause serious injuries.
Figure 11 120/240 Volt, 30 Amp, Locking Receptacle
Figure 12 120/240 Volt, 50 Amp, Receptacle