Generac QT02515ANSX Portable Generator User Manual


 
3 of 9
25 • 30 • 45 • 60 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
QT025
120/240 V, 1Ø, 1.0 pf 25 104 25 104 125
120/208 V, 3Ø, 0.8 pf 25 87 25 87 100
120/240 V, 3Ø, 0.8 pf 25 75 25 75 90
QT030
120/240 V, 1Ø, 1.0 pf 30 125 30 125 150
120/208 V, 3Ø, 0.8 pf 30 104 30 104 125
120/240 V, 3Ø, 0.8 pf 30 90 30 90 100
QT045
120/240 V, 1Ø, 1.0 pf 45 188 45 188 200
120/208 V, 3Ø, 0.8 pf 45 156 45 156 175
120/240 V, 3Ø, 0.8 pf 45 135 45 135 150
277/480 V, 3Ø, 0.8 pf 45 68 45 68 80
QT060
120/240 V, 1Ø, 1.0 pf 60 250 60 250 300
120/208 V, 3Ø, 0.8 pf 60 208 60 208 250
120/240 V, 3Ø, 0.8 pf 60 180 60 180 200
277/480 V, 3Ø, 0.8 pf 60 90 60 90 100
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
QT025
120/240 V, 1Ø 86 209
120/208 V, 3Ø 84 204
120/240 V, 3Ø 73 177
QT030
120/240 V, 1Ø 109 264
120/208 V, 3Ø 109 264
120/240 V, 3Ø 94 229
QT045
120/240 V, 1Ø 61 153
120/208 V, 3Ø 64 160
120/240 V, 3Ø 55 139
277/480 V, 3Ø 29 72
QT060
120/240 V, 1Ø 95 237
120/208 V, 3Ø 100 251
120/240 V, 3Ø 87 218
277/480 V, 3Ø 42 105
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³ /hr) (gal/hr) (l/hr)
QT025
Exercise cycle 60 1.7 0.7 2.5
25% of rated load 220 6.3 2.9 9.1
50% of rated load 297 8.4 3.3 12.3
75% of rated load 362 10.3 4 15
100% of rated load 430 12.2 4.7 17.8
QT030
Exercise cycle 60 1.7 0.7 2.5
25% of rated load 240 6.8 2.6 10
50% of rated load 320 9.1 3.5 13.3
75% of rated load 400 11.4 4.4 16.6
100% of rated load 492 14 5.4 20.4
QT045
Exercise cycle 65 1.8 0.7 2.6
25% of rated load 210 6 2.3 8.6
50% of rated load 380 10.8 4.2 15.7
75% of rated load 545 15.5 5.9 22.4
100% of rated load 730 20.7 8 30.1
QT060
Exercise cycle 123 3.5 1.34 5.1
25% of rated load 267 7.6 2.7 10.5
50% of rated load 483 13.7 5 19
75% of rated load 672 19.1 7 26.5
100% of rated load 862 24.5 9 33.9
Guardian
®
Series
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.