22 • 27 • 36 • 48 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
QT022
120/240 V, 1Ø, 1.0 pf 22 92 22 92 100
120/208 V, 3Ø, 0.8 pf 22 76 22 76 80
120/240 V, 3Ø, 0.8 pf 22 66 22 66 80
QT027
120/240 V, 1Ø, 1.0 pf 27 113 25 104 125
120/208 V, 3Ø, 0.8 pf 27 94 25 87 100
120/240 V, 3Ø, 0.8 pf 27 81 25 75 90
QT036
120/240 V, 1Ø, 1.0 pf 36 150 35 146 175
120/208 V, 3Ø, 0.8 pf 36 125 35 121 150
120/240 V, 3Ø, 0.8 pf 36 108 35 105 125
277/480 V, 3Ø, 0.8 pf 36 54 35 53 60
QT048
120/240 V, 1Ø, 1.0 pf 48 200 48 200 200
120/208 V, 3Ø, 0.8 pf 48 166.5 48 166 175
120/240 V, 3Ø, 0.8 pf 48 144 48 144 150
277/480 V, 3Ø, 0.8 pf 48 72 48 72 80
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
QT022
120/240 V, 1Ø 89 216
120/208 V, 3Ø 74 180
120/240 V, 3Ø 64 156
QT027
120/240 V, 1Ø 109 265
120/208 V, 3Ø 91 221
120/240 V, 3Ø 79 192
QT036
120/240 V, 1Ø 54 149
120/208 V, 3Ø 87 210
120/240 V, 3Ø 75 182
277/480 V, 3Ø 36 87
QT048
120/240 V, 1Ø 69 189
120/208 V, 3Ø 111 269
120/240 V, 3Ø 96 233
277/480 V, 3Ø 43 104
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft
3
/hr) (m³/hr) (gal/hr) (l/hr)
QT022
Exercise cycle 42 1.2 0.44 1.7
25% of rated load 100 2.8 1.1 4.2
50% of rated load 190 5.4 2.1 7.8
75% of rated load 255 7.2 2.8 10.5
100% of rated load 316 9 3.4 13
QT027
Exercise cycle 42 1.2 0.44 1.7
25% of rated load 108 3.1 1.2 4.5
50% of rated load 197 5.6 2.1 8.1
75% of rated load 287 8.2 3.1 11.8
100% of rated load 359 10.2 3.9 14.8
QT036
Exercise cycle 48 1.4 0.5 2
25% of rated load 156 4.4 1.7 6.4
50% of rated load 282 8 3.1 11.6
75% of rated load 392 11.1 4.3 16.2
100% of rated load 503 14.3 5.5 20.8
QT048
Exercise cycle 95 2.7 1 3.9
25% of rated load 204 5.8 2.16 8.5
50% of rated load 392 11.1 4.14 15.7
75% of rated load 547 15.5 5.8 22.8
100% of rated load 756 21.5 7.96 31.3
Quietsource
®
Series
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.