3-3
Configuring a Single
Transmitter
NOTE
See “Configuration Software” on page 2-9 for instructions on how to
install the configuration software.
To configure a single Model 244EH or 244ER transmitter, perform the
following procedure:
1. Disconnect power to the transmitter if the transmitter is installed
in a measurement loop.
NOTE
Configuring a transmitter while it is powered in a measurement loop
could cause the Model 244EC to shunt the current.
2. Set up the transmitter configuration system (see “Model 244EC
Configuration Interface” on page 2-11) and open the program.
3. Select READ FROM XMTR from the menu bar to initiate the
transmitter configuration. The main configuration window will
appear (see Figure 3-1).
Figure 3-1. Models 244EH and 244ER
Configuration Software Main
Configuration Window
4. Set the configuration parameters. To view a complete list of
options for each parameter, click the drop-down arrow in any
parameter box. For example, on the main configuration screen,
click the arrow in the UNITS box to view a list of available units.
NOTE
The configuration of the Intermittent Sensor Detect feature of the
Model 244E Temperature Transmitter with version 5.5.1 software
cannot be changed with the Model 244EC version 2.0 or earlier. For
more information see Section 4: Maintenance and Troubleshooting.
244E-244DF01