22
NOTE: Circuit board programming will not allow spa operation without
both the temperature and high limit sensors being properly connected to
the circuit board.
Once topside panel operation is veried. Turn off power, disconnect 7.
the extension loom from the circuit board and GENTLY route through
conduit to complete installation.
NOTE: This loom and its connector are not meant to withstand heavy
pulling. Make sure, when routing the extension loom and temperature
sensor lines through conduit, you exercise extreme caution.
Once properly run through the conduit, repeat steps 5 and 6 above.
In-Ground Spa Light Installation Instructions
On spas ordered with in-ground lights, the factory installs the light niche
for you. The next steps of installation should be performed by a qualied
licensed electrician.
Always read and follow light manufacturer’s safety and installation
instructions prior to installation and operation. Incorrect installation may
damage the light and void its warranty.
The light circuit must be on a GFCI protected service (alone or with a
switch).
The water resistant junction box (or for 12 volt models, the low voltage
transformer) must be located:
at least 8” (20 cm) above water level•
at least 4” (10 cm) above ground level, and•
at least 48” (121 cm) away from the spa.•
See gure below.