Briggs & Stratton 01938-0 Portable Generator User Manual


 
4
Briggs & Stratton Power Products Home Generator
Installation Manual
INSTALLATION
PROCEDURES
Unpacking Precautions
The unit is shipped bolted to its mounting pad, ready for
installation.Avoid damage from dropping, bumping, collision,
etc. Store and unpack carton with the proper side up, as
noted on the shipping carton.
Delivery Inspection
After removing the carton, carefully inspect the Home
Standby Generator for any damage that may have occurred
during shipment.
IMPORTANT: If loss or damage is noted at time of
delivery, have the person(s) making delivery note all damage
on the freight bill and affix his signature under the
consignor's memo of loss or damage. If loss or damage is
noted after delivery, separate the damaged materials and
contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment Contents
The Home Standby Generator is supplied with:
Home Standby Generator
Pre-attached mounting pad
One 24” flexible hook-up hose
Installation and start-up manual (P/N 192385GS)
Owner’s manual(P/N 192384GS)
Illustrated parts list manual (P/N 193208GS for
model 01815 or P/N 193918GS for model 01938)
Product warranty sheet (P/N 190881GS)
Installation checklist (P/N 190840GS)
Three access door keys
Four lifting hole plugs
Oil fill spout
Touch-up paint
One spare 15A fuse
Diagnostic LED kit (diode/plate/decal/pin connectors (2))
Required Specialty Tools/Equipment
Two 48” lengths of 1” OD pipe (NOT conduit)
Hole punches for 16ga steel
Torque screwdriver, 5 to 50 inch-pound range
Approved Transfer Switches
The Home Standby Generator should be used ONLY with
the following UL approved Transfer Switches. Connection
to any other transfer switch not listed below will void your
equipment warranty.
50A Nema 1 enclosure, BSPP Model 01917
50A Nema 3R enclosure, BSPP Model 01918
100A Nema 3R enclosure, BSPP Model 01813
100A Nema 3R enclosure w/ main line disconnect, BSPP
Model 01928
200A Nema 3R enclosure, BSPP Model 01814
200A Nema 3R enclosure w/ main line disconnect, BSPP
Model 01929
Home Standby Generator Location
Before installing generator, consult with homeowner and
convey the following guidelines which may affect the
desired location.
Generator Clearances
The generator enclosure must be at least 5 ft. (152 cm)
from structures having combustible walls and/or other
combustible materials. Leave at least 3 ft. (92 cm) all around
the enclosure including the roof, for adequate cooling,
generator maintenance and servicing.
Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT install
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area (Figure 1). Prevailing winds
and air currents should be taken into consideration when
positioning generator.
General Location Guidelines
Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
Installing the 15A fuse could cause the engine to start.
CAUTION
Operate generator ONLY outdoors.
Keep exhaust gas from entering a confined area through
windows, doors,ventilation intakes or other openings.
Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.
DANGER