WARNING !!!! Dealer & Service Center Use Only
SERVICE & SET UP FEATURES
LEVEL-2 ACCESS
(Includes Configuration for External Controllers)
1. Entering Service Menu:
A. To enter the service menu level, depress and hold both the Up and Down arrow keys
simultaneously until the code message [CF1] (Celsius Fahrenheit Selection) is
displayed. (NOTE: If [000] displays, User Lock Code is enabled, and the ULC pass
code must be entered before proceeding. See section: “User Lock Code Option [ULC]”,
within Level-1 operating instructions.) Depress the Pool / Spa key four times the [LOC]
code (Entrance To Service Menu) appears.
B. The [LOC] code allows service personal the ability to enter an access code to enter the
service menu. This menu includes the above-mentioned codes that have adjustable
parameters in the software that may require calibration. This section of the Menu is
intended for authorized factory service personnel only
.
C. Using the Up arrow key, scroll the displayed number to [050].
D. Once the correct service code is displayed pressing the Pool / Spa key will allow access
to the service menu. Note
: If access to service menu is denied, see number “7”, below:
“Changing Service Lock Code & “Backdoor” Entry”
E. The first service parameter displayed will be [dEL] (4 minute time delay).
NOTE: Depressing the Pool / Spa key will save the displayed value in any menu
parameter and advance to the next service menu parameters.
2. Time Delay [dEL] :
With the [dEL] (4 minute time delay) code message displayed use the Up or Down
arrow key to select either (1) to allow time delay to remain active or (0) to deactivate the
time delay. Pressing the Pool / Spa key will save the displayed selection and step to the next
service menu parameter [JAO] (Jandy and Compool Controller Interface).
CAUTION !!!: The time delay should only be deactivated for service convenience
and must
be reactivated prior to placing the heat pump back in
service. Failure to reset the time delay feature could result in
permanent damage to the heat pump compressor.
3. Configuring for External Controllers [JAO] or [FS2]:
(Also see appendix items “A” & “B”)
3.1: Configuring for External Controllers Equipped with an “OFF” Position [JAO]:
A. Follow the steps 1a. through 1d. above to enter the service menu. Once [dEL] is
displayed, press the Pool / Spa key once to display [JAO].
B. With the [JAO] ( Jandy / Compool Controller Interface) code message displayed,
use the Up or Down arrow key to select either (0) to disable the Jandy /
Compool Controller Interface, (2) to connect a thermostat type controller (two
wire connection), or (3) to connect a thermostat selector type controller (three
wire connection).
12