1-6. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.
Aftertheleaktest,applyinsulat-
ingmaterialtightlysothatthereis
no gap.
When the piping is to be at-
tached to a wall containing metals
(tinplated)ormetalnetting,use
achemicallytreatedwooden
piece20mm(7.9in.)orthicker
between the wall and the piping
or wrap 7 to 8 turns of insulation
vinyltapearoundthepiping.
To use existing piping, perform
COOL operation for 30 minutes
and pump down before removing
the old air conditioner. Remake
areaccordingtothedimension
for new refrigerant.
PARTS TO BE PROVIDED AT YOUR SITE
(A) Powersupplycord* 1
(B) Indoor/outdoor un
it connecting wire* 1
(C) Extensionpipe
(Referto1-4.) 1
(D) Wall hole cover 1
(E) Piping
tape 1
(F)
Extension drain
hose
(orsoftPVChose,15mm(19/32in.)
innerdia.orhardPVCpipeVP16)
1
(G) Refrigeration oil
Little
amount
(H) Putty 1
(I) Pipexing
band 2 to 7
(J) Fixingscrew
for(I) 2 to 7
(K) Wall hole sleeve 1
(L)
SoftPVC
hose,25mm(31/32in.)
inner dia. or hard PVC pipe VP25
1
* Note:
Placeindoor/outdoor
unitconnectingwire(B)and
powersupplycord(A)atleast1m(39.4in.)away
from the TV antenna wire.
The“Q’ty”for(B)to(K)intheabovetableisquan
-
tityto
beusedperindoorunit.
MXZ-3A30NA
More than
100 mm
(3.94in.)
Open as a rule
More than 500 mm
(19.69in.)ifthefront
and both sides are open
More than
100mm
(3.94in.)
More than
200mm
(7.87in.)ifthereare
obstacles to both sides
Open as a rule
Morethan500mm(19.69in.)iftheback,
both sides and top are open
Morethan350mm(13.78in.)
Outdoor unit installation
Air in
Air out
Air in
2-U-shape notched holes
(BaseboltM10)
2-12(0.47)
×
36
(1.42)Ovalholes
(BaseboltM10)
[Unit:mm(inch)]