USB port and cable enables UPS monitoring and unattended shutdown in the case of extended power failure
PowerAlert software available via free download from www.tripplite.com
Data line surge suppression protects standard dialup/DSL or Ethernet line connection
Built-in audible alarm and 5 front panel LEDs indicate status of line power, battery power, battery low/replace, voltage regulation and
overload
1500VA power handling ability supports a variety of sensitive electronic equipment
4.5 minutes full load runtime (1500VA), 13 minutes half load runtime (750VA)
Runtime is expandable with the addition of external battery packs (SEE OPTIONS & ACCESSORIES)
Supports hot swappable battery replacement via built-in access panel
$200,000 connected equipment insurance (USA, Puerto Rico & Canada Only)
2 year warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V AC
Frequency
compatibility
60Hz
OUTPUT
Output VA 1500
Output watts 940
Output nominal
voltage
120VAC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%), BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 8 NEMA 5-15R
INPUT
Maximum input amps 12A
Input connection type NEMA 5-15P
Input cord length 6 ft., 14 gauge
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime 4.5 minutes (1500VA / 940 watts)
Half load runtime 13 minutes (750VA / 470 watts)
Expandable battery
runtime
Extended runtime available with optional BP24V34, BP24V15RT2U, BP24V28-2U or BP24V70-3U external battery
packs
DC system voltage 24VDC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
Replacement Battery
Cartridge
RBC51 (quantity 2)
VOLTAGE REGULATION
Voltage regulation
description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without
using battery power, during brownouts to 75V and overvoltages to 147V
Overvoltage
correction
Input voltages between 128 and 147VAC are reduced by 12%
Direct pass through Input voltages between 108 and 127VAC are passed on to connected equipment unchanged