Pelco Manual C653M-D (9/03) 7
MAINTENANCE
There are no user-serviceable parts except for the fuses. If the transformer in the unit does
not work properly, contact the factory for return information. Refer to the
Warranty and
Return Information
section of this manual.
Clean the outer surface of the power supply with a nonabrasive cleaning cloth and anti-
static cleaner. Do not use kerosene or similar substances that may damage the surface.
SPECIFICATIONS
MECHANICAL
Cable Entry: Knockouts for either 1/2-inch (1.27 cm) or 3/4-inch (1.91 cm)
conduit
Fuse Size
All Fuse Models: All fuses are 5 x 20 mm
ELECTRICAL
Input Voltage
All Models: 120 or 240 VAC, 50/60 Hz
Output Voltage
MCS4-2: 24 VAC
All Other Models: 24/28 VAC
Required Input Current: See
Models
section
Table D. Required Wire Gauge
Required Wire Gauge Table (AWG)
WIRE
DIST
(feet)
CCD
Camera
P/T480
Pan/Tilt
Indoor
Spectra
PT570
Pan/Tilt
Esprit
Pan/Tilt
Indoor
XLS
CX9000
Rxr’s
Outdoor
Spectra
Equipment Loads
(VA)
10VA
1000
900
800
700
600
500
400
300
200
100
20VA 30VA 40VA 50VA 60VA 70VA 80VA 90VA 100VA 200VA
12-14
16-18
12-14
16-18
12-14
16-18
12-16
18-20
12-16
18-20
12-16
18-20
12-18
20-22
12-18
20-22
12-20
22
12-22
N/A
12
12-14
12
14-16
12
14-16
12
14-16
12
14-18
12-14
16-18
12-14
16-18
12-16
18-20
12-18
20-22
12-20
22
N/A
12-14
12
12-14
12
12-14
12
12-14
12
14-16
12
14-16
12
14-18
12-14
16-18
12-16
18-20
12-18
20-22
N/A
12
N/A
12
N/A
12
12
12-14
12
12-14
12
12-14
12
14-16
12
14-18
12-14
16-18
12-18
20-22
N/A
N/A
N/A
12
N/A
12
N/A
12
N/A
12-14
12
12-14
12
12-14
12
14-16
12-14
16-18
12-16
18-20
N/A
N/A
N/A
N/A
N/A
12
N/A
12
N/A
12
N/A
12-14
12
12-14
12
14-16
12
14-16
12-16
18-20
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12
N/A
12
12
12-14
12
12-14
12
14-16
12-16
18-20
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12
N/A
12
N/A
12
12
12-14
12
14-16
12-14
16-18
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12
N/A
12
12
12-14
12
14-16
12-14
16-18
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12
N/A
12-14
12 N/A
12-14
12-14
16-18
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12-14
12
12-14
Allowable Wire Gauge (AWG) Using 24 Volt Tap
Allowable Wire Gauge (AWG) Using 28 Volt Tap
N/A - Distance and Load Not Recommended For Any Wire Size Between 12-22 (AWG)
XX-XX
XX-XX