1500 kW Containerized
Diesel Generator Set
Fuel System
Recommended Fuel ASTM-D975/No.1 or No.2-D
Fuel Pump Maximum Lift 6.0 ft. (1.8 m)
Filter Micron Size - 98% Efficiency 2
Total Fuel Flow 183 gal/hr (693 L/hr)
Fuel Consumption (Prime Power)
At % of Load gal/hr (L/hr)
25% 29.2 (111)
50% 47.6 (180)
75% 68.0 (257)
100% 87.3 (330)
Lubrication System
Type Full Pressure System
Oil Filters 5 Spin-on Full Flow
Oil Pan Capacity 47 gal. (178 L)
Oil Capacity with Filters 54 gal. (204 L)
Oil Pressure At Rated Speed 50-70 psi (345-483 kPa)
Derating
Engine power available up to 1850 ft.
altitude and 77
o
F ambient temperature
at the Standby rating, without derating.
For operation at higher altitudes and
ambient temperatures, the power
should be derated according to the
following factors:
Altitude
Ambient
Temperature
Above 1850 ft.
derate at 6% per
1000 ft.
Above 77°F
derate at 1% per
10°F
DGC2020 Digital Genset Controller
■
Local and Remote Generator Control
■
Automatic and manual starting and stopping
■
Engine and Generator Protection
■
Programmable Analog Engine Senders
■
ECU Communications via SAE J1939
■
16 Programmable Contact Inputs
■
Programmable Logic
■
Automatic Transfer Switch Control (Mains Failure)
■
Integrated RS485 Modbus Connection
■
Auto Synchronizing
■
Event recording
Monitoring
■
Engine RPM
■
Engine run time
■
Generator voltage
■
Generator current
■
Generator frequency
■
Oil pressure
■
Battery voltage
■
Fuel level measurements
■
Running Hour Meter
■
Coolant temperature
■
Generator under/over voltage alarm/shutdown
■
Generator under/over frequency alarm/shutdown
■
Over Current alarm/shutdown
■
Warm up and cooling functions
■
Maintenance timer
Digital Controller Features
EGC1500C Rev 6
Cooling System
Exhaust Manifold Type Dry
Radiator Design Standard Horizontal
Coolant Capacity - Engine Only 37 gal. (140 L)
Water Pump Design/Type Belt Driven, Centrifugal
Coolant Flow 100 gal/min (378 L/min)
Heat Rejection to Coolant (Standby) 40600 Btu/min (715 kW)
Thermostat Range 180-200°F (82-93°C)