2 Overview (Sequence Program)
2.7 Types and Setting of Parameters
7 Setting the PLC system (1)
Click on the [PLC System(1)] tab to setup "Battery Less Mode", "Battery Mode", "MODEM Initialized", and
"RUN Terminal Input".
1) FX3S/FX3U/FX3UC PLC
2) FX
3G/FX3GC PLCs
*1. This area can be set only in FX
3U/FX3UC PLCs.
*2. This area can be set only in FX
3G/FX3GC PLCs.
*3. Up to the built-in input number of main unit.
Set item Contents of setting Setting range
Battery Less Mode
*1
Select this to operate the PLC without using the battery.
When a check mark is put here, the battery error indicator lamp is automatically
turned off and devices in the latched (battery backed) area are automatically
cleared.
Battery Mode
*2
Select this item to operate the PLC with the battery.
MODEM Initialized
Set this item to automatically initialize a connected modem when the PLC power
is turned ON.
RUN Terminal Input
Set this item to use an input terminal (X) to switch the PLC between STOP and
RUN.
None
X000 to X017
*3