9-1
9. Assigning System Devices
9.1 Addressing Extension Modules
Most of the FX famil
of PLC’s have the abilit
to connect additional discreet I/O and/or special
function modules. To benefit from these additional units the user must address each block
independentl
.
Addressing Additional Discrete I/O
This t
pe of I/O is the standard
input and output modules. As each
extension block or powered
extension unit is added to the
s
stem the
assume the next
available ad-dresses. Hence, the
units closest to the base unit will
have the lowest I/O numbers or
addresses. I/O numbers are
alwa
s counted in octal. This
means from 0 to 7 and 10 to 17
etc. Within a users pro
ram the
additional addresses are used as
normal. Discreet I/O can be added
at the users discretion as lon
as
the rules of s
stem confi
uration for each PLC t
pe are obe
ed. This information can be found
in the appropriate hardware manual.
For eas
use and identification, each additional I/O unit should be labeled with the appropriate
I/O numbers usin
the provided number labels.
Caution when using an FX system with FX-8ER, FX-24MR units
• When an FX-8ER or an FX-24MR are used an additional 8 points (as 4 inputs, 4 outputs)
of I/O must be allowed for. This is because both units split blocks of 8 inputs and 8
outputs to obtain a ph
sical 4 input/ 4 output confi
uration. Hence, an FX-8ER unit
actuall
occupies 8 input points and 8 output points even thou
h there are onl
4
ph
sical inputs and 4 ph
sical outputs.
Addressing Special Function Blocks
Special function blocks are allocated a lo
ical ‘station/block number’ from 0 to 7. This is used
b
the FROM/TO instructions to directl
access each independent special function module.
The lower the ‘station/block number’ is, the closer to the base unit it can be found. Special
function blocks can be added at the users discretion but the rules of confi
uration for each t
pe
of PLC must be obe
ed at all times. The confi
uration notes can be found in the appropriate
hardware manual for each pro
rammable controller.
POWER
FX-16EX
POWER
FX-8EX
POWER
FX-8EYT
POWER
FX-8EYR
FX-48MR
X0-27
X30-X37 X40-X57 X60-X67
Y0-Y27
Y30-Y37 Y40-Y47
FX Series Programmable Controllers