![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/f/27/f2797614-ffe4-4818-8cb7-2a5d7ce7bcd2/f2797614-ffe4-4818-8cb7-2a5d7ce7bcd2-bg63.png)
88
Limiting the output frequency
4.4.2 Avoiding mechanical resonance points (Frequency jump) (Pr. 31 to Pr. 36)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters
allow resonant frequencies to be jumped.
Parameter
Number
Name Initial Value Setting Range Description
31 Frequency jump 1A 9999 0 to 400Hz, 9999
1A to 1B, 2A to 2B, 3A to 3B is
frequency jumps
9999: Function invalid
32 Frequency jump 1B 9999 0 to 400Hz, 9999
33 Frequency jump 2A 9999 0 to 400Hz, 9999
34 Frequency jump 2B 9999 0 to 400Hz, 9999
35 Frequency jump 3A 9999 0 to 400Hz, 9999
36 Frequency jump 3B 9999 0 to 400Hz, 9999
⋅ Up to three areas may be set, with the jump frequencies set
to either the top or bottom point of each area.
⋅ The settings of frequency jumps 1A, 2A, 3A are jump points,
and operation is performed at these frequencies in the jump
areas.
Example 1 To fix the frequency to 30Hz in the range 30Hz to 35Hz, set 35Hz in Pr. 34
and 30Hz in Pr. 33.
Example 2 To jump the frequency to 35Hz in the range 30Hz to 35Hz, set 35Hz in Pr.
33 and 30Hz in Pr. 34.
CAUTION
⋅ During acceleration/deceleration, the running frequency within the set area is valid.
Pr.31
Frequency jump
Pr.32
Pr.33
Pr.34
Pr.35
Pr.36
Set frequency (Hz)
Pr.34:35Hz
Pr.33:30Hz
Pr.33:35Hz
Pr.34:30Hz