
PRO-2200 Two Reader Module PRO22R2 13Installation Guide
Single Wire Reader LED Control Configuration
tuptuODEL
>-
hgiH detatS-irT woL
DELroloCelgniSnODELffODELffODEL
DELroloC-iBnODELneerGffOsDELhtoBnODELdeR
To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader port
configuration is set via host software.
Alarm Contact Wiring
Inputs 1 to 8 may be configured to use normally open or normally closed contacts and
non-supervised or supervised (with standard ±1 tolerance 1K ohm). Four of these inputs
have default functional definitions, but all eight can be configured to monitor general-
purpose alarm sensors.
1
2
3
4
1K
1K
NO
1K
1K
NC
By default, Input 1 is defined as the Door Status Input corresponding to reader 1 and Input
2 is defined as the REX input corresponding to reader 1. Also by default, Input 3 is
defined as the Door Status Input corresponding to reader 2 and Input 4 is defined as the
REX input corresponding to reader 2.
Inputs 5, 6, 7, and 8 are general purpose inputs that can be used to monitor alarm sen-
sors or can be used as control inputs. Inputs 7 and 8 are not accessible when the board is
rack mounted.
Inputs TMP and PFL are typically used for monitoring cabinet tamper and power failure
respectively. These 2 inputs are not supervised and are not accessible when the board is
rack mounted. These inputs were primarily provided for the case when this board is
mounted remotely and can not take advantage of the tamper and power fail detect inputs
on the controller board. If these inputs are not used, install a short piece of wire at the
input to indicated safe condition.
Input configuration including debounce and hold time is set via host software.
Control Output Wiring
Six form-C relay contacts are provided for controlling door strike or other devices. Each
may be assigned to door-related functions or general-purpose output. They are
configurable as standard (energize to activate) or fail-safe (de-energize to activate) via
host software.
The energized or ON time of each relay can be configured using Pulse control for single or
repeating pulses via host software. The energized or ON time for a single pulse can be
extended up to 24 hours. For repeating pulses, the on/off time can be defined in 0.1
second increments and be repeated up to 255 times.