F50E DUCT MOUNTED ELECTRONIC AIR CLEANER
68-0072—5
20
NO
TO USE THIS CHART:
START
OFF
ON
YES
YES
REPLACE LIGHT/
SWITCH ASSEMBLY.
MAKE SURE ELECTRONIC
CELLS ARE CLEAN, DRY
AND PROPERLY INSTALLED.
MAKE SURE PREFILTERS
ARE IN SLOT ON FURNACE
SIDE OF CELLS.
TURN ON ELECTRONIC AIR
CLEANER AND SYSTEM
FAN.
CHECK NEON LIGHT.
PUSH TEST BUTTON AND
LISTEN FOR SNAPPING
SOUND.
NO
PUSH TEST BUTTON
AND LISTEN FOR
SNAPPING SOUND.
TURN OFF AIR CLEANER
AND REMOVE CELLS
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON
AIR CLEANER.
OFF
ON
OFF
ON
CHECK
ON
LED IN
W8600E
OPEN ACCESS DOOR.
CHECK
LED IN W8600E
SHOULD COME ON
3
3
1
1
1
OFF
WIRING
NOT OK
CHECK WIRING BETWEEN
W8600E AND AIR CLEANER.
USE MAX NO. 18 4-WIRE
THERMOSTAT CABLE
CONNECTED 1 TO 1,
2 TO 2, 3 TO 3, AND 4 TO 4.
WIRING OK
CORRECT
WIRING.
REPLACE
W8600E.
4
CHECK FOR CORRECT INPUT
VOLTAGE ACROSS:
120V MODELS: P1 AND P2
TERMINALS ON POWER
SUPPLY
220/240 MODELS: QUICK-
CONNECT TERMINALS ON
POWER SUPPLY
TRANSFORMER.INSPECT CELLS FOR:
BENT COLLECTOR
PLATES
BROKEN IONIZER
WIRES
DIRT ON INSULATORS
DAMAGED IONIZER
OR COLLECTOR
CONTACT TABS
YES
NO
YES
NO
FIX
WIRING.
REPAIR OR
REPLACE
CELLS.
WITH OHMMETER,
CHECK FOR SHORT
BETWEEN:
CELL FRAME AND
IONIZER SECTION
CELL FRAME AND
COLLECTOR SECTION
CELL
SHORTED
INFINITE
RESISTANCE
REPLACE
CELL.
CELL OK.
TURN OFF AIR CLEANER,
REPLACE CELLS AND
DISCONNECT FOUR W8600E
LEADS AT AIR CLEANER.
REPLACE ACCESS DOOR.
TURN ON AIR CLEANER. PUSH
TEST BUTTON AND LISTEN
FOR SNAPPING SOUND.
NO
YES
REPLACE
POWER
BOX .
AIR CLEANER OK. TURN OFF
AIR CLEANER AND RECONNECT
W8600E LEADS 1 TO 1,
2 TO 2, 3 TO 3, AND 4 TO 4.
1
THE SNAPPING SOUND ON THE AIR CLEANER, WITH A
SOLID STATE POWER SUPPLY, IS ABOUT HALF AS
LOUD AS ON MODELS WITH THE W919 POWER SUPPLY.
COMPONENTS ARE NOT FIELD REPLACEABLE.
W8600E HAS THREE LIGHT-EMITTING DIODES (LEDS):
ON, WASH, AND CHECK.
W8600E OPERATION CAN BE CHECKED SEPARATELY.
SEE W8600E INSTRUCTIONS.
2
3
4
M2002D
FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.
EACH TIME YOU ISOLATE AND FIX A PROBLEM, GO BACK TO START.
REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK.
1.
2.
3.
2
THIS STEP EXPOSES
DANGEROUSLY HIGH
VOLTAGE. ONLY A
QUALIFIED SERVICE
TECHNICIAN SHOULD
ATTEMPT THIS STEP.
WARNING
CHECK NEON LIGHT.
TURN OFF AIR CLEANER
AND REMOVE CELLS
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON AIR CLEANER.
ON
ON
WASH
LED IN W8600E
SHOULD COME ON.
OFF
ELECTRONIC AIR CLEANER
AND W8600E ARE OK.
3
TROUBLESHOOTING F50E AIR CLEANERS WITH A W8600E
SOLID STATE PERFORMANCE INDICATOR AND AIR FLOW SWITCH
Fig. 35. Electrical troubleshooting procedure for F50E electronic air cleaners with a
W8600E and solid state air flow switch.
Test Button
The TEST BUTTON is near the bottom of the access door.
When pushed, it shorts from a hot collector plate to ground.
See internal schematic, Fig. 36. The resulting arcing sound
indicates that high voltage is being supplied to the collector.
The solid state power supply controls current flow to the
collector, so the arcing sound is only about half as loud as the
sound on air cleaners with W919-style power supplies. On air
cleaners with a W8600E, the CHECK LED comes on when
the test button is pushed.
Power Supply Problem
CAUTION
Electric Shock Hazard.
Can cause personal injury.
Always turn off power and remove access door before
removing power box or its cover.