A SERVICE OF

logo

Site Planning Data, Series 610, 500-750kVA, Multi-Module Systems
102
System Control Cabinets
Multi-Module Systems are provided with a System Control Cabinet. Cabinets are available to match load current. Table 8 shows dimensions and
weights for SCCT cabinets.
Table 8 System Control Cabinet data - SCCT
Type Amps Overall dimensions - WxDxH: in. (mm) Weight - lb. (kg)
SCCT 560-1200 37x37x78 (940x940x1981) 1000 (454)
SCCT 1600 62x48x78 (1575x1219x1981) 1525 (692)
SCCT 2000 62x48x78 (1575x1219x1981) 2850 (1293)
SCCT 2500-3000 62x60x78 (1575x1524x1981) 3100 (1406)
SCCT 4000 138x60x78 (3505x1524x1981) 5850 (2653)