Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-16
Replacing a Distribution Panel
Components removed in illustration for clarity only.
Front Front
Battery
Distribution
Panel
Load
Distribution
Panel
Ground Busbar
Hardware
Ground Busbar
Hardware
Battery Busbar
Hardware
Distribution Panel
Hardware
System Load
Distribution Busbar
Hardware
Distribution Panel
Hardware
Shorting Block if 4th shelf
has Converter Option.
If more than three shelves with the
Converter Option, /48/ jumpers.
Assembly order is: lug, 1/4" flat washer, 1/4" lock washer,
1/4-20 nut. Torque to 84 in-lbs. Note that a shorting block
will be factory installed in this distribution device position.
/48/ jumpers.
Assembly order is: lug, 1/4" flat washer,
1/4" lock washer, 1/4-20 bolt.
Torque to 84 in-lbs.
List DA Dual Voltage
Distribution Panel
(Lists DB, DC, and DD similar.)