SECTION 4 ADJUSTMENTS
4 --- 1
Time Delay Adjustment
Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).
To change a setting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their cor-
responding adjustment DIP switch or potentiometer.
Table4-1.TimeDelaySettings
DESCRIPTION LABELS
FACTORY
SETTING
ADJUSTMENT
RANGE
S3 DIP
SWITCH
ADJUSTMENT
POTENTIOMETER
Override Momentar
1second Actuator 1 on
1
Normal Source Outages
3secon
s
3seconds Actuator 1 off
1
TIMER 0 minutes 0to5
rans
er to
mergency
N
E
(full ccw)
minutes
2
Override Momentary
Emergency S. Outages
— 4seconds non-adjustable — — —
TIMER 30 minutes 1secondto
etrans
er to
orma
E
N
(full cw)
30 minutes
1
Unloaded Running
(Engine Cooldown)
— 5 minutes non-adjustable — — —
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points
are set to customer specifications (if none specified,
standard factory settings are used). To change a setting,
follow procedure on page 4–2. Use Ta bles 4-2 and 4–3
for settings and corres pond ing DIP switch actuators.
NOTICE
Any change in these settings may affect the
normal operation of the automatic transfer
switch. This change could allow the load circuits
to remain connected to a low voltage source.
Table 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).
%ofnominal
S1 DIP
FACT . SET ADJ RANGE
SWITCH
95 % * Actuator 3 off
3
c
up 90 %
90 % Actuator 3 on
3
90 % *
Actuator 1 off
Actuator 2 off
21
Normal Source Voltage
85 %
Actuator 1 on
Actuator 2 off
21
DO
N D ropout
85 %
80 %
Actuator 1 off
Actuator 2 on
21
70 %
Actuator 1 on
Actuator 2 on
21
Emer
enc
Source
–– Pickup 90 % non-adjustable
Voltage
–– D ropout 75 % non-adjustable
––
–– Pickup 95 % non-adjustable
–– D ropout 85 % non-adjustable
––
Emergency Source
Frequency
60
50
60 Hz Actuator 4 off
4
Hz
60
50
z 60
z
50 Hz Actuator 4 on
4
3phase Actuator 6 off
6
o
tage
ases 3, 1 3
1 3
1phase Actuator 6 on
6
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION LABELS FACTORY SETTING AD JUSTMENT S3 DIP SWITCH
OW
LOW Actuator 2 off
2
o
tage
ust
4.2%
HI
HI Actuator 2 on
2