Series 185
CONTROLLER
(continued)
4
381333–319 E
S2 DIP s witch
S1 DIP s witch
Figure 6. DIP sw itches S1 and S2 at the top right.
The time delay settings are shown in Figures 6 and 7 and
in Table C. The sensor settings are shown in Figure 6
and in Table D. The standard (factory) settings are
showninTablesC,D,andH.
S3 DIP s witch
Figure 7. DIP sw itch S3 at the bottom center.
TableC. TimeDelaySettings
Time Delay Description Factory Setting Settings DIP Switch DIP Actuator Actuator Position
override momentary
1second S2 1 on (up)
utility outages
secon
s
3seconds S2 1 off (down)
transfer to generator 10 seconds (approx.) – – – –
override momentary
4second S3 9 on (up)
generator outages
4secon
s
0 S3 9 off (down)
transfer to utility 5 minutes (approx.) – – – –
unloaded running
2 minutes S1 10 on (up)
(generator cooldown)
m
nutes
5 minutes S1 10 off (down)
0seconds S3 7, 8 both on (up)
load disconnect delay
3seconds S3 7, 8 7on(up),8off(down)
be
ore trans
er (and delay
after transfer, if enabled)
secon
s
10 seconds S3 7, 8 7 off (down), 8 on (up)
20 seconds S3 7, 8 both off (down)
Table D. Voltage and Frequency Settings
Setting Description Setting Factory Setting Settings DIP Switch DIP Actuator Actuator Position
voltage – 220 – 240 V non–adjustable S2 2 on (up)
50 Hz S1 4 on (up)
requency nom
na
z
60 Hz S1 4 off (down)
phase – single non–adjustable S1 6 on (up)
198 V S1 3 on (up)
p
c
up
209 V * S1 3 off (down)
*
S1 1 off (down)
S1 2 off (down)
S1 1 on (up)
ut
ty vo
tage
7
S1 2 off (down)
ropout
7
S1 1 off (down)
7
S1 2 on (up)
S1 1 on (up)
54
S1 2 on (up)
pickup 198 V
generator vo
tage
dropout 165 V
non
a
usta
e
–
generator frequency pickup
57 Hz (n om 60 Hz)
48 Hz (n om 50 Hz)
dropout
51 Hz (n om 60 Hz)
43 Hz (n om 50 Hz)
non
a
usta
e
–
* If t he dropout voltage is set to 198 V, the pickup voltage must be set to 209 V.