TERMINATION CLEARANCES SIDEWALL DIRECT VENT
V X
VENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
v
v
A
G
V
FIXED
CLOSED
FIXED
CLOSED
OPERABLE
OPERABLE
V
C
B
B
B
B
F
B
V
V
A
J
V
H
M
X
X
V
V
K
B
E
D
L
DIRECT VENT
(using outdoor air for combustion)
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
Figure 9G.
Vent terminal clearances for “Direct Vent” installations. Direct Vent congurations use outdoor air for combustion.
CANADIAN INSTALLATIONS
1
US INSTALLATIONS
2
CANADIAN INSTALLATIONS
1
US INSTALLATIONS
2
A
Clearance above grade,
veranda, porch, deck or
balcony
12inches(30cm) 12inches(30cm)
H
Clearance to each side
of center line extended
above meter/regulator
assembly
3feet(91cm)withinaheight15
feet(4.5m)abovethemeter/
regulator assembly
3feet(91cm)withinaheight
15feet(4.5m)abovethe
meter/regulator assembly*
B
Clearance to window or
door that may be opened
6inches(15cm)forappliances
upto10,000Btu/hr(3kW),12
inches(30cm)forappliances
between10,000Btu/hr(3kW)
and100,000Btu/hr(30kW),36
inches(91cm)forappliances
above100,000Btu/hr(30kW)
6inches(15cm)
for appliances up to
10,000Btu/hr(3kW),
9inches(23cm)for
appliances between
10,000Btu/hr(3kW)
and50,000Btu/hr(15
kW),12inches(30cm)
for appliances above
50,000Btu/hr(15kW)
I
Clearance to service
regulator vent outlet
3feet(91cm) 3feet(91cm)*
C
Clearance to
permanently closed
window
6inches(15cm)* 6inches(15cm)*
J
Clearance to a non
mechanical air supply
inlet into building or
combustion air inlet to
any other appliance
6inches(15cm)forappliancesup
to10,000Btu/hr(3kW),12inches
(30cm)forappliancesbetween
10,000Btu/hr(3kW)and100,000
Btu/hr(30kW),36inches(91cm)
for appliances above 100,000 Btu/
hr(30kW)
6inches(15cm)for
appliances up to 10,000
Btu/hr(3kW),9inches(23
cm)forappliancesbetween
10,000Btu/hr(3kW)and
50,000Btu/hr(15kW),12
inches(30cm)forappliances
above50,000Btu/hr(15kW)
D
Vertical clearance to
ventilatedsoftlocated
above the terminal within
a horizontal distance of
2feet(61cm)fromthe
center line of the terminal
12inches(30cm)* 12inches(30cm)*
K
Clearance to a
mechanical air supply
inlet
6feet(1.83m)
3feet(91cm)aboveifwithin
10feet(3m)horizontally
E
Clearance to unventilated
soft
12inches(30cm)* 12inches(30cm)*
L
Clearance above
paved sidewalk or
paved driveway located
on public property
7feet(2.13m)† 7feet(2.13m)†*
F
Clearance to outside
corner
2feet(60cm)* 2feet(60cm)*
M
Clearance under
veranda, porch, deck,
or balcony
12inches(30cm)‡ 12inches(30cm)‡*
G
Clearance to inside
corner
8ft.(2.44m)* 8ft.(2.44m)*
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
†Aventshouldnotterminatedirectlyaboveasidewalkorpaveddrivewaythatislocatedbetweentwosinglefamilydwellingsandservesbothdwellings.
‡Permittedonlyifveranda,porch,deck,orbalconyisfullyopenonaminimumoftwosidesbeneaththeoor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.