Raypak 207A Swimming Pool Heater User Manual


 
13
Heaters must not be installed under an overhang of less than three 3 ft from the top of the heater. Three sides
must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters
installed under overhangs with the use of gutters.
For U.S. installations, the point from where the flue products exit the heater must be a minimum of 4 ft below,
4 ft horizontally from, or 1 ft above any door, window or gravity inlet into any building. The top surface of the
heater shall be at least 3 ft above any forced air inlet, or intake ducts located within 10 ft horizontally.
For installations in Canada, pool heaters shall not be installed with the top of the vent assembly within 10 ft
below, or to either side, of any opening into the building. Refer to the latest revisions of CAN/CGA-B149.1 and
B149.2.
4 ft
Minimum
4 ft
Minimum
1 ft
Minimum
4 ft
Minimum
3 ft
Minimum
10 ft
Minimum
Forced Air Inlet
For installations in Florida, that must comply with the Florida Building Code 2001, follow the directions on p14
for the installation of hurricane tie-down brackets for all models.