RECEPTACLE DETAILS
The following receptacle details are to aid in identifying mating plugs. Use this chart and compare to your genset
to determine which receptacle(s) you have. Note the NEMA configuration and use this to purchase the correct
mating plug.
NEMA 5-20R
125V - 20A
NEMA L5-30R
125V - 30A
NEMA L6-30R
250V - 30A
NEMA L6-20R
250V - 20A
NEMA 14-50R
125/250V - 50A
NEMA L14-30R
125/250V - 30A
NEMA L14-20R
125/250V - 20A
ENGINE LIMITATIONS ON GENERATOR
PERFORMANCE
Generator ratings assume 60F (20C) and Sea Level.
Operation of your generator at temperatures above 60F
(20C) or above Sea Level will result in lower electrical
output. Electrical output must be derated 2% for each 9F
above 60F and 3 ½ % for each 1000 feet above mean
sea level.
LOADING YOUR GENERATOR SET
With reference to the Receptacle details section, please
review the power receptacles fitted to your generator. The
actual load that may be pulled from each receptacle is
driven by the circuit breaker rating and the generator
rating.
DO NOT EXCEED THE INDIVIDUAL RECEPTACLE RATINGS
AS SHOWN IN THE TABLE BELOW.
DO NOT EXCEED THE TOTAL GENERATOR RATING
SHOWN IN TABLE 2 PERFORMANCE SPECIFICATIONS.
All generator units are equipped with a PUSH TO
RESET Circuit Breaker.