PM4025
Gaseous Fueled Stationary Standby
25kW
60Hz
Page 4 of 4
Alternator Data
Type Brushless Revolving Field, Drip Proof Construction
W/Tropicallized Windings
# Poles 4
Coupling Method Direct, Flex Disc
Insulation Class H, UL 1446 Recognized
Voltage Regulation
Externally Regulated, Solid State AVR ± 1.5%
Total Harmonic Distortion <3.5%
Waveform Deviation Factor <5%
Circuit Breaker Data
Type Molded Case
Withstand Rating 10kA AC @ 240v, 18kA @ 480v
Agency Listing UL 489 Listed
Control Panel Functions
• Automatic Remote Start (2-wire) • Generator Voltage Metering • Generator Frequency Metering
• Generator Current Metering • Engine Coolant Temperature Metering • Engine Coolant Temperature Protection
• Engine Oil Pressure Monitoring • Engine Oil Pressure Protection • Overspeed Protection
• Overcrank Protection • Emergency Stop Input • Engine Cooldown
• Watt Metering • VA Metering • Engine RPM Metering
• Power Factor Metering • Watt-hour Metering • Engine Run Time Metering
• Battery Voltage Metering • Battery Condition Monitoring • Maintenance Interval Timer
• On-Off-Auto Selector Switch • Low Coolant Level Detection* • Battery Charger Failure Monitoring*
Options
LP Liquid Withdrawal System
Remote Annunciation Panel – RDP110
Digital (CP1000) Panel Upgrade
Allows For:
Additional I/O Contacts
Modem Capability
Dimensions & Weight
Weight
1400 lbs.
All Specifications Subject to Change Without Notice
101-2931-0602
©2002 Coleman Powermate, Inc.
Coleman® is a registered trademark of the Coleman Company, Inc. used under license.
* Generator Set Must Be Equipped With Appropriate Hardware