PAGE 26 — DCA70USI2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (06/28/11)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Selector Switch
3-Phase 240/139V Position
Voltage Selector Switch
3-Phase 480/270V Position
Line-Line
208V 220V 240V 416V 440V 480V
Line-Neutral 120V 127V 139V 240V 254V 277V
Voltage Selector Switch Single-Phase 240/120V Position
Line-Neutral/
Line-Line
120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
Table 8. Generator Maximum Amps
Rated Voltage Maximum Amps
1Ø 120 Volt
155.5 X 2 amps (4 wire)
168 amps X 2 (Zigzag)
1Ø 240 Volt
78.8 amps (4 wire)
168 amps (Zigzag)
3Ø 240 Volt 168 amps
3Ø 480 Volt 84 amps
Table 9. 1Ø GFCI Receptacle Load Capacity
KW in Use
Twist Lock (C6369)
Available Load
Current (Amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
40.4 0
39.2 5 amps/receptacle
38.0 10 amps/receptacle
38.6 15 amps/receptacle
35.6 20 amps/receptacle
Table 10. 3Ø Generator Maximum Amps
KVA in Use
(UVWO Terminals)
Available Load
Current (Amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
70
0 amps/receptacle
65.8
5 amps/receptacle
61.7
10 amps/receptacle
57.5
15 amps/receptacle
53.4
20 amps/receptacle